As a professional supplier, we offer you this Allen Bradley 1762-IR4. This is a high-end processor with 32K memory and belonging to the SLC 5/04 series. At Feimu Technology, we understand that the loss due to a one-minute downtime of a large production line is significant. Therefore, the stability of the main controller is of the utmost importance. We don't merely sell you a stock circuit board; we provide you with a solid guarantee that can ensure the robustness of your large production line and trouble-free operation. If you need any assistance, please feel free to contact us at any time.
As a professional supplier, Feimu Technology has been deeply involved in the field of industrial control spare parts. We have recently launched the Allen Bradley 1762-IR4 - it is an RTD/resistance input module exclusive to the MicroLogix series, specifically designed to address the issues of inaccurate temperature and resistance detection and unstable signals in industrial environments. We understand that even the slightest deviation in temperature and resistance parameters on the production line can affect product quality. Therefore, we strictly control the quality of this module throughout the process.
Which PLCs are compatible?
Our tests have shown that the 1762-IR4 module has extremely strong compatibility. It is mainly compatible with the Allen Bradley MicroLogix 1100/1200/1400 series PLCs. It is an ideal expansion module for this series of PLCs, and can seamlessly connect without complex modifications. The installation method is also very convenient. It supports DIN rail or panel installation, and can be directly installed on the right side of the controller. It is small in size and does not occupy too much space in the control cabinet. Even novice engineers can complete the installation quickly.
As a supplier specializing in industrial control, we are well aware of the pain points in on-site installation. Therefore, the wiring design of this module is also very user-friendly. It adopts a screw wiring method, which ensures a firm connection and is not prone to loosening. At the same time, it reserves sufficient operation space, and the insertion and removal of cables are very convenient, significantly saving installation and debugging time.
Core parameters
Parameter Name
Specific Specifications
Product Model
Allen Bradley 1762-IR4
Product Series
MicroLogix Series
Module Type
RTD/Resistance Input Module
Input Channels
4 Channels
Compatible RTD Types
Platinum, Copper, Nickel, Nickel-Iron
Resistance Range
0-3000 Ω
Installation Method
DIN Rail / Panel Mounting
Wiring Method
Screw Connection
How about the structure and performance?
We have disassembled and tested it ourselves. The module uses high-quality circuit boards with compact and orderly component arrangement. The key chips have been reinforced, and some large electrolytic capacitors are fixed with glue, which can effectively prevent contact failures caused by vibration. Even in a high-frequency vibration environment in the workshop, it can operate stably. The gold fingers of the back bus interface on the module have a thick coating, and after insertion into the frame, they fit tightly, ensuring extremely strong electrical conductivity reliability.
Its anti-interference ability is also very excellent. It has an inter-channel isolation function, which can effectively avoid detection deviations caused by signal interference. At the same time, it supports automatic calibration. When a channel is enabled or its configuration is changed, it will automatically calibrate to ensure detection accuracy. The shell is made of industrial-grade materials, which can adapt to industrial environments of 0-55℃, dustproof and moisture-proof, and is fully compatible with the harsh working conditions of the workshop with frequent oil and dust. The products we supply are all brand new and have stable performance and a long service life.
Is it widely applicable?
Based on our practical experience, the Allen Bradley 1762-IR4 module has an extremely wide range of applications. The most common scenarios include temperature measurement and resistance detection, such as temperature monitoring in food and beverage production lines, resistance detection in water treatment systems, temperature control in automotive manufacturing conveyor lines, and equipment resistance monitoring in textile factories and printing factories.
As long as there is a need for RTD sensors or resistance input detection, and it is compatible with the MicroLogix series PLC, this module is the first choice. It can accurately collect temperature and resistance signals, convert analog signals into digital signals and transmit them to the PLC, providing precise data support for equipment control. At the same time, the product is affordable in price and has high cost-effectiveness.
FAQ
Q: Does the Allen Bradley 1762-IR4 require an additional power supply?
A: No, it doesn't need an external power supply. It is powered by the expansion bus of the MicroLogix series PLC. The wiring is done using screws, which is simple to operate and even beginners can quickly get the hang of it. We will also provide simple wiring instructions.
Q: Which types of RTD sensors are supported?
A: We support various types of RTD sensors such as platinum, copper, nickel, nickel-iron, etc. Both 2-wire, 3-wire and 4-wire RTD sensors can be compatible. The detection accuracy is high at 25℃, and it can meet the precise detection requirements in industrial sites.
Q: Is the supply of goods in stock stable?
A: For Allen Bradley 1762-IR4, the supply is stable. We rely on the logistics networks we have established with both domestic and international partners. Whether it's domestic or overseas orders, once the order is placed, the goods can be dispatched quickly to ensure that the goods can be used on-site without any delay.
Q: If the module malfunctions, can it be quickly diagnosed and resolved?
A: The module is equipped with an LED status indicator light, which can clearly show the power and channel status. It also supports open-circuit and short-circuit detection. In case of a malfunction, the problem can be quickly located, making maintenance convenient. We can also provide technical support.
RTD Wiring Guide (2-Wire, 3-Wire, 4-Wire)
The 1762-IR4 supports 2-wire, 3-wire, and 4-wire RTD connections. Each wiring method has different accuracy characteristics.
2-wire connection:
Connect both wires to IN+ and IN- terminals.
Simple wiring. Least accurate. Lead resistance adds to the reading.
Use for short cable runs (under 10 meters) or where accuracy is not critical.
3-wire connection:
Connect one wire to IN+, one to IN-, and one to IN-COM.
Compensates for lead resistance. Most common industrial method.
Recommended for most applications. Use shielded cable for runs over 10 meters.
4-wire connection:
Connect two wires to IN+ and two wires to IN-.
Most accurate. Eliminates lead resistance error.
Use for high-accuracy applications or long cable runs (over 30 meters).
Lead resistance rules:
Maximum lead resistance: 50Ω per lead (for 3-wire and 4-wire).
Exceeding 50Ω causes reading errors.
Use twisted pair shielded cable. Ground the shield at the module end only.
Avoid routing RTD cables near motor or drive power cables.
Field issue example: A customer used 2-wire connection with 25 meters of cable. The reading was 3°C high. Cause: Lead resistance added to the measurement. Fix: Switched to 3-wire connection. The reading returned to the correct value.
Temperature vs Resistance Table (Platinum RTD)
The 1762-IR4 converts resistance to temperature based on the RTD type. This table shows typical resistance values for platinum RTD at common temperatures.
Temperature (°C)
Resistance (Ω) - Platinum 100
Resistance (Ω) - Platinum 1000
-50°C
80.31Ω
803.1Ω
-20°C
92.16Ω
921.6Ω
0°C
100.00Ω
1000.0Ω
20°C
107.79Ω
1077.9Ω
40°C
115.54Ω
1155.4Ω
60°C
123.24Ω
1232.4Ω
80°C
130.89Ω
1308.9Ω
100°C
138.51Ω
1385.1Ω
120°C
146.07Ω
1460.7Ω
150°C
157.33Ω
1573.3Ω
200°C
175.86Ω
1758.6Ω
The module calculates temperature from these resistance values automatically. No manual conversion is needed. Select the correct RTD type in the software configuration.
Channel Status LEDs and Diagnostics
The 1762-IR4 has status LEDs for power and channel status. The LEDs are on the front panel, visible when installed.
Indicator
Status
Meaning
Action
PWR
Green
Module powered and operating normally.
No action needed.
PWR
Off
No power to the module.
Check PLC power. Check backplane connection.
CH0 - CH3
Green
Channel configured and reading normal.
No action needed.
CH0 - CH3
Off
Channel not configured or not used.
Configure channel in software.
CH0 - CH3
Flashing (Green)
Input signal out of range.
Check RTD wiring. Check resistance value.
CH0 - CH3
Red
Channel fault detected.
Cycle power. If red remains, check RTD for open or short.
Diagnostic functions:
Open circuit detection: Reading goes to maximum value (over-range).
Short circuit detection: Reading goes to minimum value (under-range).
This allows the PLC program to detect sensor faults and trigger alarms.
Configuration in RSLogix 500
The Allen Bradley 1762-IR4 requires software configuration in RSLogix 500. Follow these steps to set up the module.
Configuration steps:
Power off the MicroLogix controller.
Install the module on the right side of the controller.
Power on the controller.
Open RSLogix 500. Go to the I/O Configuration tree.
Right-click on the controller. Select "Add Module".
Select 1762-IR4 from the list of expansion modules.
Enter the slot position of the module (slot 1, 2, 3, etc.).
Double-click the module to open the configuration screen.
For each channel (0 to 3), select the RTD type and wiring method.
Common configuration mistake: Selecting the wrong RTD type. The module calculates temperature based on the selected RTD type. If the type does not match the physical sensor, the reading will be incorrect. Always verify the sensor type before configuring the channel.
About Feimu Technology
Feimu Technology operates from Jiangmen City, Guangdong Province, China. The company was founded in 2005 and has supplied automation components to customers in over 30 countries.
Years in operation: 20 years as of 2025.
Warehouse: 2000+ square meters. Temperature controlled. Humidity maintained below 60%.
Inventory: 5000+ active SKUs. Includes MicroLogix modules, SLC 500, CompactLogix, ControlLogix, and POINT I/O.
Brands carried: Allen Bradley, Siemens, GE, Schneider.
Export markets: Europe, North America, South America, Middle East, Southeast Asia. Over 30 countries.
Testing for 1762-IR4: Each module is visually inspected. Expansion bus test: Module connected to MicroLogix test PLC. RTD simulation test: Channels tested with precision resistance decade box. Accuracy verified at 0°C, 100°C, and 200°C. 2-wire, 3-wire, and 4-wire wiring all tested. LED functions verified. 24-hour burn-in test.
Warranty: 12 months from shipment date. Covers manufacturing defects. Does not cover wiring errors, overvoltage, physical damage, or water damage.
Contact information:
Email: sales@feimutech.com
WhatsApp: +86 13358323579
Website: www.feimuplc.com
Response time: Within 24 hours. Technical questions typically answered within 12 hours. Include module serial number and MicroLogix model when contacting.
Hot Tags: Allen Bradley 1762-IR4, Supplier, Wholesale
Feimu Technology, as a professional supplier, will respond to your inquiry quickly, provide competitive price quotes, in-stock information and product details.
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies.Privacy Policy